Abstract

In this paper, a half-scaled substructure test was performed to evaluate the failure mode of an existing transmission tower subjected to wind load. A loading scheme was devised to reproduce the dead and wind loads acting on the prototype transmission tower. The load was enforced on the model structure using two actuators and a triangular jig mounted on the reduced model. Preliminary numerical analysis was carried out to evaluate the stability and member force of the specimen for the design load. When the substructured transmission tower was loaded by 270% of its maximum allowable buckling load, local buckling occurred in joints of leg members with weak constraints. From the experimental results, such as load-displacement curves, displacements, and strains of members, it was concluded that the local buckling was due to the additional eccentric force caused by unbalanced deformation of the specimen.

Original languageEnglish
Pages (from-to)1-11
Number of pages11
JournalJournal of Constructional Steel Research
Volume65
Issue number1
DOIs
StatePublished - Jan 2009

Keywords

  • Buckling load
  • Substructure test
  • Transmission tower
  • Wind load

Fingerprint

Dive into the research topics of 'Performance evaluation of a transmission tower by substructure test'. Together they form a unique fingerprint.

Cite this