Abstract
This paper analyzes the flashover rate by lightning in Korea distribution system. Because of random characteristics of lightning, the Monte Carlo method is applied to estimate the lightning performance. The magnitude of lightning stroke is based on the curve measured in field. The classification of direct and indirect lightning depends on the striking distance. The striking distance and flashover rate are calculated by using the method based on Central Research Institute of Electric Power Industry(CRIEPI). The distribution system and lightning is modeled by using EMTP and MATLAB, and the accuracy of modeling is discussed. The simulations for the various spacing between two adjacent surge arresters and the various grounding resistance of GW according to the existence of GW are performed and the simulation results are analyzed.
| Original language | English |
|---|---|
| Pages (from-to) | 1-7 |
| Number of pages | 7 |
| Journal | Transactions of the Korean Institute of Electrical Engineers |
| Volume | 62 |
| Issue number | 1 |
| DOIs | |
| State | Published - Jan 2013 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 3 Good Health and Well-being
Keywords
- EMTP
- Flashover rate
- Lightning-induced voltage
- Overhead ground wire
- Surge arrester
Fingerprint
Dive into the research topics of 'Analysis of flashover rate by lightning in Korea distribution line using CRIEPI method'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver