Abstract
This paper analyzes a asymmetry current with SFCL (Superconducting Fault Current Limiter) operation during transient period, when a fault occurs in power systems. The principle of asymmetry current nature is reviewed and asymmetry components reduction with SFCL operation is explained. To verify the performance of SFCL, a EMTP/ATPDraw model of SFCLs using MODELS language developed and simulated. Throughout the simulation, results presents the main factors for reducing the asymmetry component of fault current are not a quenching time, but a limiting resistance of SFCL and fault initiated angle.
| Original language | English |
|---|---|
| Pages (from-to) | 450-454 |
| Number of pages | 5 |
| Journal | Transactions of the Korean Institute of Electrical Engineers |
| Volume | 58 |
| Issue number | 3 |
| State | Published - Mar 2009 |
Keywords
- Asymmetry current
- Electro-magnetic transients program(emtp)
- Superconducting fault current limiter
Fingerprint