An analysis of superconducting fault current limiter operation according to asymmetry fault current

  • Sang Bong Rhee
  • , Chul Hwan Kim
  • , Kyu Ho Kim
  • , Jae Chul Kim
  • , Ok Bae Hyun

Research output: Contribution to journalArticlepeer-review

Abstract

This paper analyzes a asymmetry current with SFCL (Superconducting Fault Current Limiter) operation during transient period, when a fault occurs in power systems. The principle of asymmetry current nature is reviewed and asymmetry components reduction with SFCL operation is explained. To verify the performance of SFCL, a EMTP/ATPDraw model of SFCLs using MODELS language developed and simulated. Throughout the simulation, results presents the main factors for reducing the asymmetry component of fault current are not a quenching time, but a limiting resistance of SFCL and fault initiated angle.

Original languageEnglish
Pages (from-to)450-454
Number of pages5
JournalTransactions of the Korean Institute of Electrical Engineers
Volume58
Issue number3
StatePublished - Mar 2009

Keywords

  • Asymmetry current
  • Electro-magnetic transients program(emtp)
  • Superconducting fault current limiter

Fingerprint

Dive into the research topics of 'An analysis of superconducting fault current limiter operation according to asymmetry fault current'. Together they form a unique fingerprint.