An adaptive reclosing technique considering the distributed generation

Research output: Contribution to journalArticlepeer-review

Abstract

The autoreclosing is applied to power system for maintaining system stability and continuity of supply. Developments on distributed generation(DG) grows significantly by environmental issues and economical issues. If the DG is connected to distribution system, the DG influences the technical aspects such as power quality, protection and stability. It causes the challenges to protection, especially to reclosing. In order to achieve reliability and safety of the distribution system, the rules and guidelines suggest that the DG units should be rapidly disconnected from the network before the reclosing. If the DG is disconnected whenever the fault occurs, it cannot be utilized effectively. This paper presents the adaptive reclosing algorithm considering the DG. The algorithm consists of angle oscillation's judgment, EEEAC(Emergency Expanded Equal-Area Criterion), calculation of optimal reclosing time and re-connection algorithm. The simulation is implemented for the DG technology by using EMTP MODELS. The simulation results show that the transient stability is maintained and the DG is protected against disturbance.

Original languageEnglish
Pages (from-to)227-232
Number of pages6
JournalTransactions of the Korean Institute of Electrical Engineers
Volume56
Issue number2
StatePublished - 2007

Keywords

  • Autoreclosing
  • Distributed generation
  • EMTP MODELS
  • Transient stability

Fingerprint

Dive into the research topics of 'An adaptive reclosing technique considering the distributed generation'. Together they form a unique fingerprint.

Cite this