A study on the overcurrent relay modeling and protective coordination for overload in domestic AC electrical railway system

Hyun Dong Kim, Gyu Jung Cho, Seung Hoon Huh, Chul Hwan Kim

Research output: Contribution to journalArticlepeer-review

Abstract

In this paper, modeling of overcurrent relay(OCR) to protect domestic AC electric railway Auto Transformer(AT) feeding system and operation characteristic analysis on overload condition are described. The target system of this paper is actual site where overload trip of circuit breaker occurs frequently. Because this AT feeding system is made of parallel single track which had a load(electric train) respectively, and is connected with only T phase of Scott Transformer. In addition, this system has been feeding 66kV voltage by KEPCO, not 154kV. We focus on protective coordination of Scott Transformer primary side and secondary side OCR for Korea single track AC electrical railway system in operation currently. We modeled single track AT feeding system and OCR. Also we performed faults and overload analysis for verification of OCR's setting values and system modeling. To analyze above mentioned research, we used PSCAD/EMTDC software tool.

Original languageEnglish
Pages (from-to)1121-1127
Number of pages7
JournalTransactions of the Korean Institute of Electrical Engineers
Volume65
Issue number7
DOIs
StatePublished - Jul 2016

Keywords

  • At feeding system
  • OCR
  • PSCAD/EMTDC
  • Scott transformer

Fingerprint

Dive into the research topics of 'A study on the overcurrent relay modeling and protective coordination for overload in domestic AC electrical railway system'. Together they form a unique fingerprint.

Cite this